A boiler losing pressure regularly means you have a problem with the boiler or the central heating system. The most common reason is a leak, which could be anywhere on the system. I have been a full-time heating engineer for over a decade, and a boiler losing pressure is normally easy to fix.
Causes for pressure dropping
Bleeding radiators will cause your boiler pressure to drop, but if it keeps dropping, there is something else causing it.
Most likely causes:
- A Leak
- Expansion vessel has lost its air
- Pressure relief valve passing water
- Filling loop letting by
A leak
The most common problem I get called out to on a boiler that keeps losing pressure is a leak. This could be anywhere; a radiator, a radiator pipe under the floor, the boiler, literally anywhere on the heating system.
The most common place for a heating system leak is on a radiator valve. Check them all for any signs of water. You can often fix a leaking radiator valve by tightening a nut on the valve. There are usually three nuts on a radiator valve that can leak and be fixed by tightening the nut.

If the leak is not on a radiator, check under the boiler and any other heating pipes on show around the house. If you can’t find the leak, it could be under the floor. This means the floor will have to come up, or, you can try adding some leak sealer to the system if it’s a small leak.
Expansion vessel
A pressurised central heating system needs an expansion vessel to take the expansion of the hot water when the heating is turned on. If your pressure is dropping with no leaks, a faulty expansion vessel is the most likely cause. These are either inside the boiler or could be in the hot water cylinder cupboard if you have one.
The expansion vessel should be full of air, so when the heating is on it takes some of the pressure increase away from the radiators and pipes. If it loses air (quite common), your boiler pressure will rise too high when you turn the heating on, causing it to reach over 3 bar. This will cause the pressure relief valve safety device to release all the water (pressure) outside and take your pressure gauge to 0.
To fix this problem, you need to recharge your expansion vessel by pumping it up with a pump. If that doesn’t work and the diaphragm inside the vessel is split, you will have to replace the expansion vessel.

Pressure relief valve passing
All pressurised heating systems must have a safety device called a pressure relief valve (PRV). A PRV protects your system from building up too much pressure and causing a radiator or boiler to blow up. PRVs can leak because they get little bits of debris or dirt stuck in them when they open to release the high pressure.
Slow Pressure Drop? If your boiler pressure keeps dropping slowly and it’s not rising to 3 bar first, you should check your copper blow-off (overflow) pipe outside for dripping water. If it’s dripping, you will need to replace the pressure relief valve. Make sure the pressure is not rising before replacing it because the new PRV will leak if something is causing the pressure to rise.

Filling loop letting by
Another reason for losing pressure could be your filling loop being slightly open or broken. This will cause the pressure to rise to 3 bar and the PRV to blow the system water outside. Sometimes the valves on the filling loop are not closed properly after topping the pressure up, and sometimes the valve just doesn’t close fully anymore because of dirt or damage and the filling loop valve needs to be replaced.

Pressure rising first
If your boiler pressure is rising to 3 bar this is most often caused by your expansion vessel not doing its job. It could also be caused by the filling loop constantly letting water into the heating system, but this is less common. When your pressure rises to 3 bar the PRV will let the water and pressure out of your heating system. The PRV sometimes will not close fully after being used, so after fixing the pressure rising problem, you might have to replace the PRV also.

Conclusion
If your boiler loses pressure constantly, finding out the cause is the first step to fixing it. If there is no sign of water coming out of the copper pipe outside, it is most likely a leak. If the pressure is rising to 3 bar when the heating is turned on, it’s the expansion vessel.
Have any questions? Drop them in the comments below, I’ll do my best to help! If you found this post helpful, don’t forget to share it with others who might benefit.
FAQs
Can a dripping tap cause boiler pressure to drop?
No, a dripping tap can not cause boiler pressure to drop. A tap is not connected to your central heating system, so a kitchen or bathroom tap dripping cannot affect your boiler pressure.
How often should a boiler lose pressure?
A boiler should never lose pressure unless there is a problem. If your central heating is losing pressure, you might have a leak on the heating system. If it loses pressure once or twice a year, I wouldn’t worry about it.
Is low boiler pressure dangerous?
No, low boiler pressure is not dangerous. If your boiler pressure is too low the boiler will not work, but it will not make it dangerous. You should repressurise the boiler if you have low pressure to stop it from breaking down.




My boiler losses pressure if it’s not been used very much
Hi I have a new combo boiler fitted, all was ok until we bled the radiators due to the towel rail in the bathroom having a cold spot. The next day we had no pressure in the boiler so we topped it up and all was ok until two days later we woke up to no pressure. We have topped it up again and checked the radiators, we can’t see any leaking from the valves? Can the valves be leaking without water leaking from them??
Hi Karen,
No, the valves won’t be leaking if there’s no water. If you’ve just had a new boiler fitted then it could just be air in the system working its way out of awkward places depending on the size and layout of your heating system. See what it’s like over the next few weeks but it could be a leak on a pipe under the floor somewhere.
Is 15 mm pipe? I found one but is nothing leak there, is ok?
Yeah, 15mm. Check it for leaks next time you notice the boiler pressure dropping.
Pressure is slowly dropping every day, when I use heating system, is something else what I can check? All parts inside the boiler looks dry when I check, also last year I had issue with heater plate, so I removed and cleaned is possible is something with this part?
Yes, it can potentially be a pinhole leak on the plate heat exchanger causing the pressure to drop. The heat exchanger will need to be replaced if it’s leaking.
Thank you for help, Can be very small leak on the plate and I can’t see sny sign of water?will back here when I change heat plate and I let you know or is better. All the best for you
Thank you Steven, can be very small leak on the heat plate and is hard to see? I will back here to let you know or is better when I change heat plate
You won’t see a leak because it’s on the inside of the plate. It’s going from the heating side of the heat exchanger to the hot water side.
You’re welcome and good luck!
Hi Steven
Is it normal to top your boiler pressure over a period of time .
Or does indicate a leak .
Appreciate your feed back
Thankyou
Hi Jason,
Your pressure shouldn’t be dropping at all but if your boiler keeps losing pressure then there is definitely a problem, most likely a leak.
Hi Steven, I changed heat plate but after few hours again pressure dropping, any idea what else I can do?
Hi Lukasz,
Are you sure you isolated the flow and return valves on the boiler properly?
If the leak is on the boiler then it will either be coming out of the blow-off pipe outside or the plate heat exchanger.
Yes, Steven, I close First one from the left and the last one, also I keep checking all the time blow off pipe and is nothing there, is this pipe? https://forum.buildhub.org.uk/uploads/monthly_2019_06/20190622_232022.jpg.d1d777b238b60f3a088305a775628fbb.jpg Heat exchanger plate is dry as well, do I have to top up expanssion vessel after I changed heat plate?
Yes, that’s the blow-off pipe. Did you top the boiler pressure up to 2 bar when everything was cold then isolate it overnight?
Hi
My boiler pressure keeps dropping. Yesterday I topped the water and after the first heat cycle and the second the pressure was down to 0. I have also noticed water dripping outside. Any suggestions?