Worcester boiler low pressure gauge

Why Does My Boiler Keep Losing Pressure? Common Causes

Last updated on January 4th, 2025

A boiler losing pressure regularly means you have a problem with the boiler or the central heating system. The most common reason is a leak, which could be anywhere on the system. I have been a full-time heating engineer for over a decade, and a boiler losing pressure is normally easy to fix.

Causes for pressure dropping

Bleeding radiators will cause your boiler pressure to drop, but if it keeps dropping, there is something else causing it.

Most likely causes:

  • A Leak
  • Expansion vessel has lost its air
  • Pressure relief valve passing water
  • Filling loop letting by

A leak

The most common problem I get called out to on a boiler that keeps losing pressure is a leak. This could be anywhere; a radiator, a radiator pipe under the floor, the boiler, literally anywhere on the heating system.

The most common place for a heating system leak is on a radiator valve. Check them all for any signs of water. You can often fix a leaking radiator valve by tightening a nut on the valve. There are usually three nuts on a radiator valve that can leak and be fixed by tightening the nut.

Old leaking radiator valve
Old leaking radiator valve

If the leak is not on a radiator, check under the boiler and any other heating pipes on show around the house. If you can’t find the leak, it could be under the floor. This means the floor will have to come up, or, you can try adding some leak sealer to the system if it’s a small leak.

Expansion vessel

A pressurised central heating system needs an expansion vessel to take the expansion of the hot water when the heating is turned on. If your pressure is dropping with no leaks, a faulty expansion vessel is the most likely cause. These are either inside the boiler or could be in the hot water cylinder cupboard if you have one.

The expansion vessel should be full of air, so when the heating is on it takes some of the pressure increase away from the radiators and pipes. If it loses air (quite common), your boiler pressure will rise too high when you turn the heating on, causing it to reach over 3 bar of pressure. This will cause the pressure relief valve safety device to release all the water (pressure) outside and take your pressure gauge to 0.

To fix this problem, you need to recharge your expansion vessel by pumping it up with a pump. If that doesn’t work and the diaphragm inside the vessel is split, you will have to replace the expansion vessel.

Recharging Worcester boiler expansion vessel
Recharging expansion vessel

Pressure relief valve passing

All pressurised heating systems must have a safety device called a pressure relief valve (PRV). A PRV protects your system from building up too much pressure and causing a radiator or boiler to blow up. PRVs can leak because they get little bits of debris or dirt stuck in them when they open to release the high pressure.

Slow Pressure Drop? If your boiler pressure keeps dropping slowly and it’s not rising to 3 bar first, you should check your copper blow-off (overflow) pipe outside for dripping water. If it’s dripping, you will need to replace the pressure relief valve. Make sure the pressure is not rising before replacing it because the new PRV will leak if something is causing the pressure to rise.

PRV copper blow off pipe
PRV blow-off pipe

Filling loop letting by

Another reason for losing pressure could be your filling loop being slightly open or broken. This will cause the pressure to rise to 3 bar and the PRV to blow the system water outside. Sometimes the valves on the filling loop are not closed properly after topping the pressure up, and sometimes the valve just doesn’t close fully anymore because of dirt or damage and the filling loop valve needs to be replaced.

Baxi boiler with bucket and filling loop underneath
Filling loop under a boiler

Pressure rising first

If your boiler pressure is rising to 3 bar this is most often caused by your expansion vessel not doing its job. It could also be caused by the filling loop constantly letting water into the heating system, but this is less common. When your pressure rises to 3 bar the PRV will let the water and pressure out of your heating system. The PRV sometimes will not close fully after being used, so after fixing the pressure rising problem, you might have to replace the PRV also.

Boiler pressure too high on 3 bar

Conclusion

If your boiler loses pressure constantly, finding out the cause is the first step to fixing it. If there is no sign of water coming out of the copper pipe outside, it is most likely a leak. If the pressure is rising to 3 bar, it’s most likely the expansion vessel.

Have any questions? Drop them in the comments below, I’ll do my best to help! If you found this post helpful, don’t forget to share it with others who might benefit.

FAQs

Can a dripping tap cause boiler pressure to drop?

No, a dripping tap can not cause boiler pressure to drop. A tap is not connected to your central heating system, so a kitchen or bathroom tap dripping cannot affect your boiler pressure.

How often should a boiler lose pressure?

A boiler should never lose pressure unless there is a problem. If your central heating is losing pressure, you might have a leak on the heating system. If it loses pressure once or twice a year, I wouldn’t worry about it.

Is low boiler pressure dangerous?

No, low boiler pressure is not dangerous. If your boiler pressure is too low the boiler will not work, but it will not make it dangerous. You should repressurise the boiler if you have low pressure to stop it from breaking down.

Author

  • Steven Reid HouseWarm Plumber

    I am a full-time plumber and Gas Safe registered engineer. I incorporated HouseWarm Ltd. in 2011 to provide heating and plumbing services to homes in Newcastle upon Tyne, England. I now blog about what I've learned over the years to help DIYers and plumbers.

Share this post

80 thoughts on “Why Does My Boiler Keep Losing Pressure? Common Causes”

  1. Steve Pope

    Over this weekend of very cold weather, my combi boiler has lost pressure 4 times, it is located in the loft.
    I can not find any sign of a leak on any pipe or radiator. No signs of any leaks on exposed pipes in the loft.
    I have used the filling loop to refill the boiler to 1 bar each time..there is a few drops of water from the filling loop levers when opened but stop when the filling loop is closed.
    To check how much condensate was being produced, I diverted the condensate pipe into a plastic bucket, and not as much as 2 litres an hour, but a fair amount was produced.

    Any ideas what I should do while I wait to get a gas engineer out

    1. Steven Reid

      You can only keep repressurising the boiler until the problem is found and fixed.

      The filling loop leaking won’t be causing the pressure to drop but a leak could be anywhere on the pipes under the floor.

      You should check if the pressure is rising to 3 bar before dropping

      1. Steve Pope

        Thanks for the quick response, will keep filling as suggested until I can get a gas engineer. I just rechecked the filling loop. It’s wet on the cold mains side, not on the heating side. So I’m happy that the filling loop is not the problem.

        1. Steven Reid

          It could still be a filling loop problem if it’s leaking at all. I thought you meant it’s only leaking when you top the pressure up. If it’s leaking all the time then it’s probably a faulty filling loop valve problem.

  2. When the heating comes on the pressure guage goes to 1.5bar
    When the heating goes off pressure guage goes back down to 0
    The engineer from BG came and pumped water out of the expansion tank and said it should now be ok
    The problem after a couple of days has reverted to the original situation as above .. BG can’t come back until the first week in January .
    Is there anything I should do? Should I add water to the system?

    1. Steven Reid

      Sounds like the pressure relief valve is letting the water outside if the pressure is not rising to 3 bar first. This is normal after having expansion vessel problems, sometimes the pressure relief valve doesn’t close properly after being used and it will need to be replaced.

      You’ll just have to keep topping the pressure up until it gets fixed.

  3. Zuher Panju

    Thanks for such a speedy reply. I’ll mention it to the bg engineer. The next date they have given me is 21/12. In the meantime can I just keep topping up? I’m s vulnerable adult and need to have my heat on?

    1. Steven Reid

      You’re welcome. Yes, you can keep topping the pressure up.

      Good luck!

  4. Zuher Panju

    As a follow up I had the bg engineer come and fix a leak in the downstairs radiator. Another engineer came to finish the job as the nut was still leaking. There has been no further leaks but no one topped the water and a substantial amount of water came out of the radiator. But in the last 3 weeks the pressure issue has been a bigger problem

    1. Steven Reid

      Hi Zuher,
      Sounds like an expansion vessel or pressure relief valve problem causing the pressure to keep dropping, possibly both.

      You should top the pressure up and turn the heating on at the maximum temperature setting on the boiler, then wait to see how much the pressure rises.

      If it rises to 3 bar then you will need to recharge the expansion vessel, or possibly replace it.

      If the pressure does not rise to 3 bar and starts leaking outside, then you will need to replace the pressure relief valve.

  5. Zuher Panju

    Hi
    My boiler pressure keeps dropping. Yesterday I topped the water and after the first heat cycle and the second the pressure was down to 0. I have also noticed water dripping outside. Any suggestions?

  6. Hi Steven, I changed heat plate but after few hours again pressure dropping, any idea what else I can do?

    1. Steven Reid

      Hi Lukasz,
      Are you sure you isolated the flow and return valves on the boiler properly?

      If the leak is on the boiler then it will either be coming out of the blow-off pipe outside or the plate heat exchanger.

        1. Steven Reid

          Yes, that’s the blow-off pipe. Did you top the boiler pressure up to 2 bar when everything was cold then isolate it overnight?

  7. Thank you Steven, can be very small leak on the heat plate and is hard to see? I will back here to let you know or is better when I change heat plate

    1. Steven Reid

      You won’t see a leak because it’s on the inside of the plate. It’s going from the heating side of the heat exchanger to the hot water side.

      You’re welcome and good luck!

      1. Hi Steven
        Is it normal to top your boiler pressure over a period of time .
        Or does indicate a leak .
        Appreciate your feed back
        Thankyou

        1. Steven Reid

          Hi Jason,
          Your pressure shouldn’t be dropping at all but if your boiler keeps losing pressure then there is definitely a problem, most likely a leak.

  8. Is 15 mm pipe? I found one but is nothing leak there, is ok?

    1. Steven Reid

      Yeah, 15mm. Check it for leaks next time you notice the boiler pressure dropping.

      1. Pressure is slowly dropping every day, when I use heating system, is something else what I can check? All parts inside the boiler looks dry when I check, also last year I had issue with heater plate, so I removed and cleaned is possible is something with this part?

        1. Steven Reid

          Yes, it can potentially be a pinhole leak on the plate heat exchanger causing the pressure to drop. The heat exchanger will need to be replaced if it’s leaking.

          1. Thank you for help, Can be very small leak on the plate and I can’t see sny sign of water?will back here when I change heat plate and I let you know or is better. All the best for you